Codal provision /IS-CODE recommendation for slab as per IS-456:2000
In this article we discussed Codal provision /IS-CODE recommendation for slab as per IS-456:2000
Minimum area of reinforcement
for Fe-415 = 0.12% of gross area(B*D)
for Fe-250 = 0.15% of gross area(B*D)
Maximum area of reinforcement = 4% (not given in IS-code)
Maximum diameter of steel bars in slab = Thickness of slab/8
Maximum spacing of the reinforcement in main bars are minimum of :-
- 3d
- 300mm
Maximum spacing of the reinforcement in distribution bars are minimum of :-
- 5d
- 300
d= effective depth of slab( total depth - effective cover)
IS-code recommendation for slab as per IS-456:2000